Multi-speed select – Hitachi L300P User Manual

Page 142

Advertising
background image

Using Intelligent Input Terminals

Oper

ations

a

nd Moni

tor

ing

4–12

Multi-Speed
Select

The inverter can store up to 16 different fixed target frequencies (speeds) in parameters A020
to A035. Binary inputs select the speed through four of the intelligent terminals configured as
binary-encoded inputs CF1 to CF4 per the table. These can be any of the five inputs, and in any
order. You can use fewer inputs if you need eight or fewer speeds.

NOTE: When choosing a subset of speeds to use, always start at the top of the table, and with
the least-significant bit: CF1, CF2, etc.

The example with eight speeds in the figure below shows how input switches configured for
CF1 – CF3 functions can change the motor speed in real time.