Hitachi L300P User Manual

Page 143

Advertising
background image

L300P Inverter

Oper

ati
ons

and Monitor

ing

4–13

.

While using the multi-speed capability, you can monitor the output frequency with monitor
function D001 during each segment of a multi-speed operation.
There are two ways to program the speeds into the registers A020 to A035:

1. Standard keypad programming:

a. Select each parameter A020 to A035.
b. Press the

key to view the parameter value.

c. Use the

and

keys to edit the value.

d. Use the

key to save the data to memory.

2. Programming using the CF switches:

a. Turn the Run command OFF (Stop Mode).
b. Turn inputs ON to select desired Multi-speed. Display the value of F001 on the digital

operator.

c. Set the desired output frequency by pressing the

and

keys.

d. Press the

key once to store the set frequency. When this occurs, F001 indicates the

output frequency of the selected Multi-speed.

e. Press the

key once to confirm that the indication is the same as the set frequency.

f. Repeat operations in 2. a) to 2. e) to set the frequency of other Multi-speeds. It can be set

also by parameters A020 to A035 in the first procedure 1. a) to 1. d).

Opt.

Code

Symbol

Function Name

Input

State

Description

02

CF1

Binary speed select,
Bit 0 (LSB)

ON

Bit 0, logical 1

OFF

Bit 0, logical 0

03

CF2

Binary speed select,
Bit 1

ON

Bit 1, logical 1

OFF

Bit 1, logical 0

04

CF3

Binary speed binary
select, Bit 2

ON

Bit 2, logical 1

OFF

Bit 2, logical 0

05

CF4

Binary speed select,
Bit 3 (MSB)

ON

Bit 3, logical 1

OFF

Bit 3, logical 0

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

F001, A020 to A035
A019=00

Notes:
When programming the multi-speed settings,

be sure to press the Store key each time and
then set the next multi-speed setting. Note
that when the Store key is not pressed, no
data will be set.

When a multi-speed setting more than

50Hz(60Hz) is to be set, it is necessary to
program the maximum frequency A04 high
enough to allow that speed.

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

CF3

CF4

CF1

CF2

(LSB)

(MSB)

Example (some CF inputs require input
configuration; some are default inputs—
see page

3–43

):

FUNC.

1

2

STR

1

2

STR

FUNC.