Analog signal calibration settings – Hitachi L300P User Manual

Page 123

Advertising
background image

“C” Group: Intelligent Terminal Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–54

Analog Signal
Calibration
Settings

The functions in the following table configure the signals for the analog output terminals. Note
that these settings do not change the current/voltage or sink/source characteristics – only the
zero and span (scaling) of the signals.

NOTE: Settings C081, C082, C083, C121, C122, C123 are factory-calibrated for each inverter.
Do not change these settings unless absolutely necessary. Note that if you restore factory
defaults for all parameters, these settings will not change.

“C” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

C081

[O] input span calibra-
tion

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C081 O-ADJUST

TOP 02119

C082

[OI] input span calibra-
tion

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C082 OI-ADJUST

TOP 02512

C083

[O2] input span calibra-
tion

Range is 0 to 65530

✔ ✔

Factory-calibrated

>C083 O2-ADJUST

TOP 02818

C085

Thermistor input tuning

Range is 0.0 to 1000

✔ ✔

105.0

105.0

105.0

>C085 THERM

ADJUST 0105.0

C086

[AM] terminal offset
tuning

Range is 0.0 to 10.0V

✔ ✔

0.0

0.0

0.0

V

>C086 AM-MONITOR

OFFSET 00.0V

C087

[AMI] terminal meter
tuning

Range is 0.0 to 250%

✔ ✔

80.

80.

80.

%

>C087 AMI-MON

ADJUST 080

C088

[AMI] terminal offset
tuning

Range is 0 to 20mA

✔ ✔

Factory-calibrated

mA

>C088 AMI-MON

OFFSET 04.0mA

C121

[O] input zero calibra-
tion

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C121 O-ADJUST

ZERO 00000

C122

[OI] input zero calibra-
tion

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C122 OI-ADJUST

ZERO 00000

C123

[O2] input zero calibra-
tion

Range is 0 to 6553 (65530)

✔ ✔

Factory-calibrated

>C123 O2-ADJUST

ZERO 03622