Troubleshooting
Tips

The table below lists typical symptoms and the corresponding solution(s).

Symptom/condition

Probable Cause

Solution

The motor

will not run.

The inverter

outputs U, V, W

are not supplying

voltage.

Is the frequency command source

A001 parameter setting correct?

Is the Run command source A002

parameter setting correct?

Make sure the parameter

setting A001 is correct.

Make sure the parameter

setting A002 is correct.

Is power being supplied to terminals

[R], [S], and [T] ([L1], [L2], and
[L3])? If so, the POWER lamp should
be ON.

Check terminals [R], [S], and

[T] ([L1], [L2], and [L3]), then
[U], [V], and [W] ([T1], [T2],
and [T3]).

Turn ON the power supply or

check fuses.

Is there an error code

EXX.X

displayed?

Press the Func. key and deter-

mine the error type. Eliminate
the error cause, then clear the
error (Reset).

Are the signals to the intelligent input

terminals correct?

Is the Run Command active?

Is the [FW] terminal (or [RV])

connected to P24 (via switch, etc.)

Verify the terminal functions

for C001 - C005 are correct.

Turn ON Run command

enable.

Supply 24V to [FW] or [RV]

terminal, if configured.

Has the frequency setting for F001

been set greater than zero?

Are the control circuit terminals [H],

[O], and [L] connected to the potenti-
ometer?

Set the parameter for F001 to a

safe, non-zero value.

If the potentiometer is the

frequency setting source, verify
voltage at [O] > 0V.

Is the RS (reset) function or FRS (free-

run stop) function ON?

Turn OFF the command(s).

Inverter outputs
U, V, W are
supplying voltage.

Is the motor load too heavy?

Reduce load or test the motor

independently of the load.

The direction of the motor is

reversed.

Are the connections of output termi-

nals [U/T1], [V/T2], and [W/T3]
correct?

Is the phase sequence of the motor

forward or reverse with respect to
[U/T1],[V/T2], and [W/T3]?

Make connections according to

the phase sequence of the
motor. In general:
FWD = U-V-W, and REV=U-
W-V.

Are the control terminals [FW] and

[RV] wired correctly?

Is parameter F004 properly set?

Use terminal [FW] for forward,

and [RV] for reverse.

Set motor direction in F004.