Serial communications – Hitachi L300P User Manual

Page 122

Advertising
background image

L300P Inverter

Configur

ing Dr

iv

e

P

a

ra

met

e

rs

3–53

Serial
Communications

The following table configures the communications port of the L300P inverter. You can have up
to thirty-two devices on the serial communications network. The inverters are slaves and the
computer or digital operator is the master. Thus, all inverters on the serial connection must use
the same baud rate, data length, parity, and stop bits. However, each device on the serial
network must have a unique node address. Please see Appendix B for more information.

“C” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

C070

Data command method

Four option codes:
02 Digital operator
03 RS485
04 Expansion Card #1
05 Expansion Card #2

✘ ✘

02

02

02

>C070 PARAM

SELECT REM

C071

Communication speed
selection

Five option codes:
02 (Test)
03 2400bps
04 4800bps
05 9600bps
06 19200bps

✘ ✔

04

04

04

bps

>C071 RS485

BAU 4800bps

C072

Node allocation

Set the address of the
inverter on the network.
Range is 1 to 32.

✘ ✔

1.

1.

1.

>C072 RS485

ADDRESS 01

C073

Communication data
length selection

Two option codes:
07 7-bit data
08 8-bit data

✘ ✔

7

7

7

>C073 RS485

BIT 7BIT

C074

Communication parity
selection

Three option codes:
00 No parity
01 Even parity
02 Odd parity

✘ ✔

00

00

00

>C074 RS485

PARITY NO

C075

Communication stop bit
selection

Two option codes:
01 1 stop bit
02 2 stop bits

✘ ✔

1

1

1

>C075 RS485

STOPBIT 1BIT

C078

Communication wait
time

Time the inverter waits after
receiving a message before it
transmits. Range is 0.0 to
1000 ms

✘ ✔

0.

0.

0.

>C078 RS485

WAIT 0000ms