[AM] and [AMI]
Terminals

The [AM] and [AMI] terminals provide signals
to monitor various inverter parameters such as
output frequency, output current, and output
voltage. The terminals provide these analog
signal types:

• [AM] terminal: 0–10V analog output signal

• [AMI] terminal: 4–20mA analog output

signal

These signals both use the [L] terminal for signal
return. Six different inverter parameters may be
monitored independently at either the [AM] or
[AMI] terminal, as listed in the table below. Use
C028 to configure terminal [AM], and C029 to configure terminal [AMI].

The analog signals may need some adjustment for gain or offset to compensate for variances in
the system. For example, the signals may drive a panel meter and require a full-scale gain
adjustment. The table below lists the function codes and their descriptions. The [AM] and
[AMI] terminals have separate gain and offset adjustments. Note the default values.

Func.

Terminal

Code

Description

Full Scale Value

C028 /

C029

[AM] /

[AMI]

00

Output frequency

0 – Max. frequency (Hz)

01

Output current

0 – 200%

04

Output voltage

0 – 100%

05

Input electric power

0 – 200%

06

Thermal load ratio

0 – 100%

07

LAD frequency

0 – Max. frequency (Hz)

Func.

Terminal

Description

Range

Default

B080

[AM]

Gain adjustment

0 – 255

180

C086

[AM]

Offset Adjustment

0.0 – 10.0V

0.0V

C087

[AMI]

Gain adjustment

0 – 255

80

C088

[AMI]

Offset Adjustment

0.0 – 20.0mA

0.0mA

H O2

FM

AM

O

OI

L

AMI

A GND

See I/O specs on page