CAUTION: Do not insert leading power factor capacitors or surge absorbers between the
output terminals of the inverter and motor.

CAUTION: Be sure to connect the grounding terminal to earth ground.

CAUTION: When inspecting the unit, be sure to wait five minutes after tuning OFF the power
supply before opening the cover.

CAUTION: SUPPRESSION FOR NOISE INTERFERENCE FROM INVERTER
The inverter uses many semiconductor switching elements such as transistors and IGBTs. Thus,
a radio receiver or measuring instrument located near the inverter is susceptible to noise inter-
ference.
To protect the instruments from erroneous operation due to noise interference, they should be
used well away from the inverter. It is also effective to shield the whole inverter structure.
The addition of an EMI filter on the input side of the inverter also reduces the effect of noise
from the commercial power line on external devices.
Note that the external dispersion of noise from the power line can be minimized by connecting
an EMI filter on the primary side of inverter.

Power

Input

Inverter

L1, L2, L3

Ground fault

interrupter

U, V, W

Motor

GND lug

Surge absorber

Leading power

factor capacitor

GFI

Power

source

R1

EMI filter

S1

T1

R2

S2

T2

L1

L2

L3

U

V

W

Motor

Inverter

Inverter

Remote

operator

EMI filter

noise

Motor

Conduit or shielded cable—
to be grounded

Grounded frame

Completely ground the enclosed
panel, metal screen, etc. with as
short a wire as possible.