Configur

ing Dr

iv

e

P

a

ra

met

e

rs

3–51

Output Function
Adjustment
Parameters

The following parameters work in
conjunction with the intelligent output
function, when configured. The
overload level parameter (C041) sets the
motor current level at which the
overload signal [OL] turns ON. The
range of settings is from 0% to 200% of
the rated current for the inverter. This
function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are available on other functions).

The frequency arrival signal, [FA1] to
[FA5], is intended to indicate when the
inverter output has reached (arrived at)
the target frequency. You can adjust the
timing of the leading and trailing edges
of the signal via two parameters specific
to acceleration and deceleration ramps,
C042 and C043.

The Error for the PID loop is the magni-
tude (absolute value) of the difference
between the Setpoint (desired value)
and Process Variable (actual value). The
PID output deviation signal [OD]
(output terminal function option code
04) indicates when the error magnitude
has exceeded a magnitude you define.

0

Motor

current

Overload

signal

1

C041

t

0

Output

frequency

Arrival

signal

1

C042

C043

t

0

PID Error

(PV-SP)

Deviation

Signal

1

SP

C044

t

“C” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

C040

Overload signal output
mode

Choose when the overload
signal is enabled; two option
codes:
00 During accel/decel
01 During constant speed

✘ ✔

01

01

01

>CO40 OL

Mode CRT

C041

Overload level setting

Range is 0.00 * rated current
to 2.00 * rated current

✘ ✔

Rated current for

each inverter

A

>C041 OL

LEVEL 0016.5A

C042

Frequency arrival
setting for acceleration

Sets the frequency arrival
setting threshold for the
output frequency during
acceleration

✘ ✔ 0.00 0.00 0.00

Hz

>C042 ARV

ACC 0000.00Hz

C043

Arrival frequency
setting for deceleration

Sets the frequency arrival
setting threshold for the
output frequency during
deceleration

✘ ✔ 0.00 0.00 0.00

Hz

>C043 ARV

DEC 0000.00Hz