Overload advance notice signal – Hitachi L300P User Manual

Page 169

Advertising
background image

L300P Inverter

Oper

ati
ons

and Monitor

ing

4–39

Overload
Advance Notice
Signal

When the output current exceeds a
preset value, the [OL] or [OL2]
terminal signal turns ON. The parame-
ter C041 (or C111, respectively) sets
the overload threshold. The overload
detection circuit operates during
powered motor operation and during
regenerative braking. The output
circuits use open-collector
transistors, and are active low.

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to
prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s
output transistor.

Opt.

Code

Symbol

Function Name

Output

State

Description

03

OL

Overload advance
notice signal (1)

ON

when output current is more than the set
threshold for the overload signal (C041)

OFF

when output current is less than the set
threshold for the overload signal (C041)

Valid for
outputs:

11, 12, AL0 – AL2

Required
settings:

C041

Notes:
The default value is 100%. To change the

level from the default, set C041 (overload
level).

The accuracy of this function is the same as

the function of the output current monitor on
the [FM] terminal (see

“Analog Output

Operation” on page 4–54

).

power running

Set

value

[OL]

Signal

regeneration

Current

threshold

threshold

C041

C041

ON

ON

t

OL

See I/O specs on page

4–8

.

Inverter output terminal circuit

12C

12A

11C

11A

24VDC

L

Example (requires output configuration—
see page

3–48

):

+