Analog output operation, Fm] terminal, Pwm signal type – Hitachi L300P User Manual

Page 184: Analog output operation 4–54, Analog output

Advertising
background image

Analog Output Operation

Oper

ations

a

nd Moni

tor

ing

4–54

Analog Output Operation

In the system design for inverter applications it is sometimes useful to monitor inverter opera-
tion from a remote location. In some cases, this requires only a panel-mounted analog meter
(moving-coil type). In other cases, a controller device such as a PLC may monitor and
command the inverter frequency and other functions. The inverter can transmit the (real-time)
output frequency, current, or other parameters to the controller to confirm actual operation. The
monitor output terminal [FM] serves these purposes.

[FM] Terminal

The inverter provides an analog/digital output on
terminal [FM] (frequency monitor). It uses
terminal [CM1] as digital GND reference. While
many applications use this terminal to monitor
the output frequency, you can configure terminal
[FM] to transmit one of several parameters.
Most use pulse-width modulation (PWM) to
represent the value, while one parameter uses
frequency modulation (FM) to represent the
value. Do not confuse the notation for terminal
[FM] (with brackets) with FM signal type.

The following table lists the configurations for terminal [FM]. Use function C027 to configure.

PWM Signal Type

The pulse-width modulated signal at terminal
[FM] is primarily designed for driving a moving-
coil meter. The pulse-width modulated signal is
automatically averaged by the inertia of the
moving-coil mechanism—converting the PWM
signal to an analog representation. Be sure to use
a 10V full-scale DC voltmeter.

The signal characteristics of terminal [FM] in
PWM signal configuration is shown below

Func.

Code

Description

Waveform

Full Scale Value

C027

00

Output frequency

PWM

0 – Max. frequency (Hz)

01

Output current

PWM

0 – 200%

03

Output frequency

FM

0 – Max. frequency (Hz)

04

Output voltage

PWM

0 – 100%

05

Input electric power

PWM

0 – 200%

06

Thermal load ratio

PWM

0 – 100%

07

LAD frequency

PWM

0 – Max. frequency (Hz)

See I/O specs on page

4–8

.

D GND

Analog/digital Output

H O2

FM

AM

O

OI

L

FW

TH

PLC

P24

CM1

AMI

H O2

FM

AM

O

OI

L

FW

TH

PLC

P24

CM1

AMI

+

0 to 10V,

1 mA

0 V

time

[FM]

10V

T

t

[FM] output value

t

T

---

=

Period T = 6.4ms constant (156 Hz)

Selects FM type output

= [FM] terminal 8-bit gain setting

B081

C27=00, 01, 04, 05, 06, 07