Hitachi EMC Recommendations

Appendix D

D–4

Hitachi EMC Recommendations

WARNING: This equipment should be installed, adjusted, and serviced by qualified personal
familiar with construction and operation of the equipment and the hazards involved. Failure to
observe this precaution could result in bodily injury.

Use the following checklist to ensure the inverter is within proper operating ranges and
conditions.

1. The power supply to L300P inverters must meet these specifications:

• Voltage fluctuation+/- 10% or less

• Voltage imbalance +/- 3% or less

• Frequency variation +/- 4% or less

• Voltage distortion THD = 10% or less

2. Installation measure:

• Use a filter designed for L300P inverter.

3. Wiring:

• Shielded wire (screened cable) is required for motor wiring, and the length must be less

than 50 meters.

• The carrier frequency setting must be less than 5 kHz to satisfy EMC requirements.

• Separate the power input and motor wiring from the signal/process circuit wiring.

4. Environmental conditions—when using a filter, follow these guidelines:

• Ambient temperature: –10 to 40 °C

• Humidity: 20 to 90% RH (non-condensing)

• Vibration: 5.9 m/sec

2

(0.6 G) 10 ~ 55Hz, L300P–110xxx to L300P–300xxx

2.94 m/sec

2

(0.3 G) 10 ~ 55Hz, L300P–370xxx to L300P–1320xxx

• Location: 1000 meters or less altitude, indoors (no corrosive gas or dust)