Free-run Stop

When the terminal [FRS] is turned ON, the inverter turns OFF the output and the motor enters
the free-run state (coasting). If terminal [FRS] is turned OFF, the output resumes sending power
to the motor if the Run command is still active. The free-run stop feature works with other
parameters to provide flexibility in stopping and starting motor rotation.

In the figure below, parameter B088 selects whether the inverter resumes operation from 0 Hz
(left graph) or the current motor rotation speed (right graph) when the [FRS] terminal turns
OFF. The application determines the best setting.

Parameter B003 specifies a delay time before resuming operation from a free-run stop. To
disable this feature, use a zero delay time.

FRS

Switches

Motor

speed

[FW, RV]

Zero-frequency start

FRS

Switches

Motor

speed

Resume from current speed

wait time

[FW, RV]

B003

B088=01

B088=00

Resume from 0Hz

t

t

Opt.

Code

Symbol

Function Name

Input

State

Description

11

FRS

Free-run Stop

ON

Causes output to turn OFF, allowing
motor to free run (coast) to stop

OFF

Output operates normally, so controlled
deceleration stops motor

Valid for inputs:

C001, C002, C003, C004,
C005

Required
settings:

B003, B088, C011 to C015

Notes:
When you want the [FRS] terminal to be

active low (normally closed logic), change the
setting (C011 to C015) that corresponds to
the input (C001 to C005) that is assigned the
[FRS] function.