Three-wire interface operation – Hitachi L300P User Manual

Page 158

Advertising
background image

Using Intelligent Input Terminals

Oper

ations

a

nd Moni

tor

ing

4–28

Three-wire
Interface
Operation

The 3-wire interface is an industry standard motor control interface. This function uses two
inputs for momentary contact start/stop control, and a third for selecting forward or reverse
direction. To implement the 3-wire interface, assign 20 [STA] (Start), 21 [STP] (Stop), and 22
[F/R] (Forward/Reverse) to three of the intelligent input terminals. Use momentary contact for
Start and Stop. Use a selector switch, such as SPST for the Forward/Reverse input. Be sure to
set the operation command selection A002=01 for input terminal control of motor.

If you have a motor control interface that needs logic-level control (rather than momentary
pulse control), use the [FW] and [RV] inputs instead.

The diagram below shows the use of 3-wire control. STA (Start Motor) is an edge-sensitive
input; an OFF-to-ON transition gives the Start command. The control of direction is level-
sensitive, and the direction may be changed at any time. STP (Stop Motor) is also a level-
sensitive input.

Opt.

Code

Symbol

Function Name

Input

State

Description

20

STA

Start Motor

ON

Start motor rotation on momentary
contact (uses acceleration profile)

OFF

No change to motor operation

21

STP

Stop Motor

ON

No change to motor operation

OFF

Stop motor rotation on momentary contact
(uses deceleration profile)

22

F/R

Forward/Reverse

ON

Select reverse direction of rotation

OFF

Select forward direction of rotation

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

A002=01

Notes:
The STP logic is inverted. Normally the

switch will be closed, so you open the switch
to stop. In this way, a broken wire causes the
motor to stop automatically (safe design).

When you configure the inverter for 3-wire

interface control, the dedicated [FW] terminal
is automatically disabled. The [RV] intelligent
terminal assignment is also disabled.

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

STA

F/R

STP

Example (requires input configuration—
see page

3–43

):

[STA] terminal

[F/R] terminal

[STP] terminal

Motor revolution speed

Forward

Reverse

t