Selecting functions and editing parameters, A 0 0 1, A 0 0 3 – Hitachi L300P User Manual

Page 65

Advertising
background image

Using the Front Panel Keypad

In

v

e

rt

er Moun

ting

and Install

a

tion

2–26

Selecting
Functions and
Editing Parame-
ters

In order to run the motor for the powerup test, this section will show how to:

• select the inverter’s maximum output frequency to the motor

• select the keypad potentiometer as the source of motor speed command

• select the keypad as the source of the RUN command

• set the number of poles for the motor

• enable the RUN command

The following series of programming tables are designed for successive use. Each table uses
the previous table’s final state as the starting point. Therefore, start with the first and continue
programming until the last one. If you get lost or concerned that some of the other parameters
settings may be incorrect, refer to

“Restoring Factory Default Settings” on page 6–9

.

CAUTION: If you operate a motor at a frequency higher than the inverter standard default
setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective
manufacturer. Only operate the motor at elevated frequencies after getting their approval.
Otherwise, there is the danger of equipment damage.

Setting the Motor Base Frequency -The motor is designed to operate at a specific AC
frequency. Most commercial motors are designed for 50/60 Hz operation. First, check the
motor specifications. Then follow the steps in the table below to verify the setting or correct for
your motor. DO NOT set it for greater than 50/60 Hz unless the motor manufacturer specifi-
cally approves operation at the higher frequency.

TIP: If you need to scroll through a function or parameter list, press and hold the

or

key to auto-increment through the list.

Action

Display

Func./Parameter

Press the

key.

Monitor functions

Press the

or

keys until ->

“A” Group selected

Press the

key.

First “A” parameter

Press the

key twice.

Base frequency setting

Press the

key.

or

Default value for base frequency
US = 60 Hz, Europe = 50 Hz

Press the

or

key as needed.

Set to your motor specs (your
display may be different)

Press the

key.

Stores parameter, returns to “A”
Group list

FUNC

d

0 0 1

1

2

A – – –

FUNC

A 0 0 1

1

A 0 0 3

FUNC

6 0

5 0

1

2

6 0

STR

A 0 0 3

1

2