“C” Group: Intelligent Terminal Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–50

Note 1: To ensure safe inverter operation in networked applications, you cannot change an

intelligent terminal assignment to/from [RMD] (option code 27) via the network.
However, you can still read an [RMD] output assignment over the network.

Analog Summary Table - The following table shows all seven functions available for assign-
ment to the three analog output terminals [FM], [AM], [AMI] at a glance. Detailed descrip-
tions, related parameters and settings, and example wiring diagrams are in

“Analog Output

Operation” on page 4–54

.

13

THM

Thermal alarm signal

ON

when the thermal limit for the motor is exceeded

OFF

when the thermal limit is not exceeded

27

RMD

*1

Run command source
monitor
(–xFU2 and –xFE2
models only)

ON

when the Run command source is the operator keypad
(A002=02)

OFF

when the Run command source is not the operator
keypad (A002=01, 03, 04, or 05)

Output Function Summary Table

Option

Code

Terminal

Symbol

Function Name

Description

Analog Output Function Summary Table

Option

Code

Function Name

Description

Corresponding Signal

Range

00

Output frequency

Actual motor speed, represented by PWM
signal

0 to max. frequency in Hz

01

Output current

Motor current (% of maximum rated output
current), represented by PWM signal

0 to 200%

03

Digital output
frequency

Output frequency (available only at FM
output)

0 to max. frequency in Hz

04

Output voltage

Rated output voltage to motor

0 to 100%

05

Input power

Rated input power

0 to 200%

06

Electronic thermal
overload

Percentage of electronic overload attained

0 to 100%

07

LAD frequency

Internal ramp generator frequency

0 to max. frequency in Hz