Using Intelligent Output Terminals

Oper

ations

a

nd Moni

tor

ing

4–44

In the following examples, t

0

= instantaneous power failure time, t

1

= allowable under-voltage /

power failure time (B002), and t

2

= retry wait time (B003).

Opt.

Code

Symbol

Function Name

Output

State

Description

08

IP

Instantaneous
Power Failure

ON

when the inverter detects a loss of input
power

OFF

when the inverter has input power

09

UV

Under-voltage
condition

ON

when the inverter input power is less than
the specified input range

OFF

when the inverter input power is within
the voltage specification

Valid for
outputs:

11, 12, AL0 – AL2

Required
settings:

B001, B002, B003, B004,
B005, B007

Notes:
If an over-voltage or over-current trip occurs

during the deceleration and an instantaneous
power failure error (E16) is displayed the
inverter goes into free-run stop. In this case
make the deceleration time longer.

When connecting control power supply

terminal [Ro]-[To] to the DC bus [P]-[N], an
under-voltage may be detected at power-off
and cause a trip. If this is undesirable, set
B004 to 00 or 02.

Frequency matching: The inverter reads the

motor RPM and direction. If this speed is
higher than the matching setting (B007), the
inverter waits until they are equal and then
engages the output to drive the motor
(example 3). If the actual motor speed is less
than the restart frequency setting, the inverter
waits for t

2

(value in B003) and restarts from

0 Hz (example 4). The display shows

oooo

” during an actual frequency

matching event.

UV

IP

See I/O specs on page

4–8

.

Inverter output terminal circuit

12C

12A

11C

11A

24VDC

L

L

Example (requires output configuration—
see page

3–48

):

+

Power supply

Inverter output

Motor

frequency

After waiting for t

2

seconds when t

0

< t

1

; restart

Example 1: Power failure within allowed limits; resume

Example 2: Power failure longer than limits; trip

t

0

t

1

t

2

Power supply

Inverter output

Motor

frequency

t

0

t

1

Inverter trips when t

0

> t

1

Free-run

Free-run