Monitoring trip events, history, & conditions, Fault detection and clearing, Error status codes – Hitachi L300P User Manual

Page 207: Error codes, Monitoring trip events, history, & conditions 6–5, Monitoring trip events, history, Monitoring

Advertising
background image

L300P Inverter

T

roub

leshooting

and Maintenance

6–5

Monitoring Trip Events, History, & Conditions

Fault Detection
and Clearing

The microprocessor in the inverter detects a
variety of fault conditions and captures the event,
recording it in a history table. The inverter output
turns OFF, or “trips” similar to the way a circuit
breaker trips due to an over-current condition.
Most faults occur when the motor is running (refer
to the diagram to the right). However, the inverter
could have an internal fault and trip in Stop Mode.
In either case, you can clear the fault by pressing
the Stop/Reset key. Additionally, you can clear the
inverter’s cumulative trip history by performing the procedure

“Restoring Factory Default

Settings” on page 6–9

(setting B_84=00 will clear the trip history but leave inverter settings

intact).

Error Status
Codes

The conditions at the time of an error provide important clues to help you understand the cause.
The L300P inverter displays a “status at trip point” digit to the right of the decimal point for
some error codes. For example,

E07.2

means Error 7 occurred and the inverter status was

condition # “2” when the error occurred.

Error Codes

An error code will appear on the display automatically when a fault causes the inverter to trip.
The following table lists the cause associated with the error.

Run

Stop

RUN

STOP

RESET

Trip

Fault

STOP

RESET

Fault

Status
Codes

Inverter Status

Status

Codes

Inverter Status

---.0

Reset

---.5

f0 stop

---.1

Stop

---.6

Starting

---.2

Deceleration

---.7

DC braking

---.3

Constant speed

---.8

Overload restriction

---.4

Acceleration

---.9

Auto-tuning

Error

Code

Name

Probable Cause(s)

E01

Over current event while at
constant speed

The inverter output was short-circuited, or the
motor shaft is locked or has a heavy load. These
conditions cause excessive current for the inverter,
so the inverter output is turned OFF.

The dual-voltage motor is wired incorrectly.

Note: The L300P will over current trip at
nominally 150% of rated current.

E02

Over current event during
deceleration

E03

Over current event during
acceleration

E04

Over current event during
other conditions

DC braking power(A054) is set too high, or a
current transformer error occurred, or a noise
source induced the error.

E05

Overload protection

When a motor overload is detected by the
electronic thermal function, the inverter trips and
turns OFF its output.

Advertising