Using Intelligent Output Terminals

Oper

ations

a

nd Moni

tor

ing

4–50

Run Command
Source Monitor
(–xFU2 models
only)

The Run Command Source Monitor intelligent output provides a way to monitor the present
setting for the Run Command Source Setting parameter (A002). Some applications use devices
external to the inverter, such as intelligent keypads or network control hosts, which can change
the A002 parameter setting at various times in normal operation. In the control environment of
the inverter, a Hand/Auto or Manual/Auto mode change requires writing a new A002 setting.
So, the intelligent output Run Command Source Monitor provides a way for external devices to
know whether the inverter’s Run command source is the operator keypad (A002=02), or some
other source (A002=01, 03, 04, or 05).

Opt.

Code

Symbol

Function Name

Output

State

Description

27

RMD

Run command
source monitor

ON

when the Run command source is the
operator keypad (A002=02)

OFF

when the Run command source is not the
operator keypad (A002=01, 03, 04, or 05)

Valid for
outputs:

11, 12, AL0 – AL2

Required
settings:

A002

Notes:
This function is available only on –xFU2

models.

The Run Command Source Monitor output

can serve as a Hand/Auto or Manual/Auto
input to a building automation system.

To ensure safe inverter operation in

networked applications, you cannot change
an intelligent terminal assignment to/from
[RMD] (option code 27) via the network.
However, you can still read an [RMD] output
assignment over the network.

RMD

See I/O specs on page

4–8

.

Inverter output terminal circuit

12C

12A

11C

11A

24VDC

L

Example (requires output configuration—
see page

3–48

):

+