Output deviation for pid control – Hitachi L300P User Manual

Page 170

Advertising
background image

Using Intelligent Output Terminals

Oper

ations

a

nd Moni

tor

ing

4–40

Output Deviation
for PID Control

The PID loop error is defined as the
magnitude (absolute value) of the differ-
ence between the Setpoint (target value)
and the Process Variable (actual value).
When the error magnitude exceeds the
preset value for C044, the [OD] terminal
signal turns ON. Refer to

“PID Loop

Operation” on page 4–58

.

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode to
prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s
output transistor.

Opt.

Code

Symbol Function Name

Output

State

Description

04

OD

Output deviation
for PID control

ON

when PID error is more than the set
threshold for the deviation signal

OFF

when PID error is less than the set thresh-
old for the deviation signal

Valid for
outputs:

11, 12, AL0 – AL2

Required
settings:

C044

Notes:
The default deviation value is set to 3%. To

change this value, change parameter C044
(deviation level).

Process variable

Set

value

[OD]

Signal

Setpoint

Error

(SP-PV)

C044

C044

ON

ON

t

OD

See I/O specs on page

4–8

.

Inverter output terminal circuit

12C

12A

11C

11A

24VDC

L

Example (requires output configuration—
see page

3–48

):

+

Advertising