Circuit breaker and fuse sizes, Wire connectors, Motor overload protection – Hitachi L300P User Manual

Page 15

Advertising
background image

xiv

Circuit Breaker
and Fuse Sizes

The inverter’s connections to input power must include UL Listed inverse time circuit breakers
with 600V rating, or UL Listed fuses as shown in the table below.

Wire Connectors

WARNING: Field wiring connections must
be made by a UL Listed and CSA Certified
ring lug terminal connector sized for the
wire gauge being used. The connector must
be fixed using the crimping tool specified by
the connector manufacturer.

Motor Overload
Protection

Hitachi L300P inverters provide solid state motor overload protection, which depends on the
proper setting of the following parameters:

• B012 “electronic overload protection”

• B212 “electronic overload protection, 2nd motor”

Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is
0.2 * rated current to 1.2 * rated current.

WARNING: When two or more motors are connected to the inverter, they cannot be protected
by the electronic overload protection. Install an external thermal relay on each motor.

Input

Voltage

Motor

Output

200V

Inverter Models,

L300P

Circuit

Breaker

(A)

Fuse

(A)

Input

Voltage

Motor

Output

400V

Inverter Models,

L300P

Circuit

Breaker

(A)

Fuse

(A)

HP

kW

HP

kW

200V

2

1.5

-015LFU2

10

10

400V

2

1.5

-015HFU2, HFE2

10

10

3

2.2

-022LFU2

15

15

3

2.2

-022HFU2, HFE2

10

10

5

3.7

-037LFU2

20

20

5

4.0

-040HFU2, HFE2

15

15

7.5

5.5

-055LFU2

30

30

7.5

5.5

-055HFU2, HFE2

15

15

10

7.5

-075LFU2

40

40

10

7.5

-075HFU2, HFE2

20

20

15

11

-110LFU2

60

60

15

11

-110HFU2, HFE2

30

30

20

15

-150LFU2

70

70

20

15

-150HFU2, HFE2

35

35

25

18.5

-185LFU2

90

90

25

18.5

-185HFU2, HFE2

50

50

30

22

-220LFU2

100

100

30

22

-220HFU2, HFE2

50

50

40

30

-300LFU2

150

150

40

30

-300HFU2, HFE2

70

70

50

37

-370LFU2

175

175

50

37

-370HFU2, HFE2

80

80

60

45

-450LFU2

200

200

60

45

-450HFU2, HFE2

100

100

75

55

-550LFU2

250

250

75

55

-550HFU2, HFE2

125

125

100

75

-750LFU2

300

300

100

75

-750HFU2, HFE2

150

150

125

90

-900HFU2, HFE2

200

150

110

-1100HFU2, HFE2

225

175

132

-1320HFU2, HFE2

300

Terminal (ring lug)

Cable support

Cable