“H” Group: Motor Constants Functions

Configur

ing Dr

iv

e

P

a

ra

meters

3–56

“H” Group: Motor Constants Functions

Introduction

The “H” Group parameters configure the
inverter for the motor characteristics. You
must manually set H003 and H004 values
to match the motor. The remaining H206
parameters are factory-set. If you want to
reset the parameters to the factory default
settings, use the procedure in

“Restoring

Factory Default Settings” on page 6–9

.

Output

V/f control,

constant torque

V/f control,

variable torque

V/f control, free-

setting curve

Inverter Torque Control Algorithms

02

01

00

A044

“H” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

H003 Motor capacity, 1st

motor

Select 0.2 to 75.0 kW for
models up to –550xxx,
0.2 to 160.0 kW for models
–900xxx to –1320xxx

✘ ✘

Factory set

kW

>H003 AUX

K 003.70kW

H203 Motor capacity, 2nd

setting

Select 0.2 to 75.0 kW for
models up to –550xxx,
0.2 to 160.0 kW for models
–900xxx to –1320xxx

✘ ✘

Factory set

kW

>H203 2AUX

K 003.70kW

H004 Motor poles setting, 1st

motor

Four selections:
2 / 4 / 6 / 8

✘ ✘

4

4

4

Poles

>H004 AUX

P 4P

H204 Motor poles setting, 2nd

motor

Four selections:
2 / 4 / 6 / 8

✘ ✘

4

4

4

Poles

>H204 2AUX

P 4P

H006 Motor stabilization

constant, 1st motor

Motor constant (factory set),
range is 0 to 255

✔ ✔ 100. 100. 100.

>H006 AUX

KCD 00100

H206 Motor stabilization

constant, 2nd motor

Motor constant (factory set),
range is 0 to 255

✔ ✔ 100. 100. 100.

>H206 2AUX

KCD 00100