CAUTION: When a loss of phase occurs, increased ripple current will markedly reduce main
capacitor life over time. Diode bridge failure can also result. If phase loss occurs under load,
the inverter could be damaged. Please pay particular attention to the setting of function B006.

Electronic
Thermal Overload
Alarm Setting

The thermal overload detection protects
the inverter and motor from overheating
due to an excessive load. It uses a current/
inverse time curve to determine the trip
point. The thermal overload alarm [THM]
is the resulting intelligent output.

First, use B013 to select the torque
characteristic that matches your load.
This allows the inverter to utilize the best
thermal overload characteristic for your
application.

B002

Allowable under-
voltage power failure
time

The amount of time a power
input under-voltage can
occur without tripping the
power failure alarm. If
under-voltage exists longer
than this time, the inverter
trips, even if the restart
mode is selected. If it exists
less than this time retry will
be attempted. Range is 0.3 to
1.0 sec.

✘ ✔

1.0

1.0

1.0

sec.

>b002 IPS

TIME 1.0s

B003

Retry wait time before
motor restart

Time delay after a trip
condition goes away before
the inverter restarts the
motor.
Range is 0.3 to 100 seconds.

✘ ✔

1.0

1.0

1.0

sec.

>b003 IPS

WAIT 001.0s

B004

Instantaneous power
failure / under-voltage
trip alarm enable

Three option codes:
00 Disable
01 Enable
02 Disable during stop and

ramp to stop

✘ ✔

00

00

00

>b004 IPS

TRIP OFF

B005

Number of restarts on
power failure / under-
voltage trip events

Two option codes:
00 Restart 16 times
01 Always restart

✘ ✔

00

00

00

>b005 IPS

RETRY 16

B006

Phase loss detection
enable

Two option codes:
00 Disable – no trip on

phase loss

01 Enable – trip on phase

loss

✘ ✔

00

00

00

>b006 PH-FAIL

SELECT OFF

B007

Restart frequency
threshold

When the frequency of the
motor is less than this value,
the inverter will restart at
0 Hz.
Range is 0.00 to 400.0 Hz

✘ ✔ 0.00 0.00 0.00

Hz

>b007 IPS

F 0000.00Hz

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Units

SRW Display

Func.

Code

Name

Description

–FE2

(CE)

–FU2

(UL)

–FR

(Jpn)

x 1.0

0

Output frequency

Hz

x 0.8

x 0.6

5

20

60

120

Constant torque

Reduced

torque

B013=01

B013=00

Trip current

reduction

factor