Reset inverter – Hitachi L300P User Manual

Page 156

Advertising
background image

Using Intelligent Input Terminals

Oper

ations

a

nd Moni

tor

ing

4–26

Reset Inverter

The [RS] terminal causes the inverter to
execute the reset operation. If the inverter is
in Trip Mode, the reset cancels the Trip
state. When the signal [RS] is turned ON
and OFF, the inverter executes the reset
operation. The minimum pulse width for
[RS] must be 12 ms or greater. The alarm
output will be cleared within 30 ms after the
onset of the Reset command.

WARNING: After the Reset command is given and the alarm reset occurs, the motor will
restart suddenly if the Run command is already active. Be sure to set the alarm reset after
verifying that the Run command is OFF to prevent injury to personnel.

Opt.

Code

Symbol

Function Name

Input

State

Description

18

RS

Reset Inverter

ON

The motor output is turned OFF, the Trip
Mode is cleared (if it exists), and powerup
reset is applied

OFF

Normal power-on operation

Valid for
inputs:

C001, C002, C003, C004,
C005

Required
settings:

B003, B007, C102, C103

Notes:
When the control terminal [RS] input is

already ON at powerup for more than 4
seconds, the remote operator display is “R-
ERROR COMM<2>” (the display of the
digital operator is – – – –). However, the
inverter has no error. To clear the digital
operator error, turn OFF the terminal [RS]
input and press one of the operator keys.

The active edge (leading or trailing) of the [RS] signal is determined by the setting of

C102.

A terminal configured with the [RS] function can only be configured as a normally open

contact. The terminal cannot be used in the normally closed contact state.

When input power is turned ON, the inverter performs the same reset operation as it does

when a pulse on the [RS] terminal occurs.

12 ms minimum

approx. 30 ms

[RS]

Alarm output

t

5

3

1

4

2

FW

TH

PLC

P24

CM1

See I/O specs on page

4–8

.

RS

Example: (default input configuration
shown—see page

3–43

):