H 0 0 3, H 0 0 4 – Hitachi L300P User Manual

Page 67

Advertising
background image

Using the Front Panel Keypad

In

v

e

rt

er Moun

ting

and Install

a

tion

2–28

Configure the Inverter for the Number of Motor Poles- The number of magnetic poles of a
motor is determined by the motor’s internal winding arrangement. The specifications label on
the motor usually indicates its number of poles. For proper operation, verify the parameter
setting matches the motor poles. Many industrial motors have four poles, corresponding to the
default setting in the inverter.

Follow the steps in the table below to verify the motor poles setting and change it if necessary
(the table resumes action from the end of the previous table.)

This step concludes the parameter setups for the inverter. You are almost ready to run the motor
for the first time!

TIP: If you became lost during any of these steps, first observe the state of the PRG LED. Then
study the

“Keypad Navigational Map” on page 2–25

to determine the current state of the

keypad controls and display. As long as you do not press the STR key, no parameters will be
changed by keypad entry errors. Note that power cycling the inverter will not cause it to reset to
a particular programming state.

The next section will show you how to monitor a particular parameter from the display. Then
you will be ready to run the motor.

Action

Display

Func./Parameter

Press the

key.

“A” Group selected

Press the

key three times.

“H” Group selected

Press the

key.

First “H” parameter

Press the

key once.

Motor poles parameter

Press the

key.

2 = 2 poles
4 = 4 poles (default)
6 = 6 poles
8 = 8 poles

Press the

or

key as needed.

Set to match your motor (your
display may be different)

Press the

key.

Stores parameter, returns to “H”
Group list

FUNC

A – – –

1

h – – –

FUNC

h 0 0 3

1

h 0 0 4

FUNC

4

1

2

4

STR

h 0 0 4