Run time / power-on time over signals – Hitachi L300P User Manual

Page 176

Advertising
background image

Using Intelligent Output Terminals

Oper

ations

a

nd Moni

tor

ing

4–46

Run Time /
Power-On Time
Over Signals

L300P Series inverters accumulate the total hours in Run Mode (run time) and the total hours of
power-ON time. You can set thresholds for these accumulating timers. Once the threshold is
exceeded, an output terminal will turn ON. One use of this is for preventative maintenance. A
signal light or audible alert could signal the need for servicing, calibration, etc.

Opt.

Code

Symbol

Function Name

Output

State

Description

11

RNT

Run Time Over

ON

when the accumulated time spent in Run
Mode exceeds the limit (B034)

OFF

when the accumulated time in Run Mode
is still less than the limit (B034)

12

ONT

Power-ON Time
Over

ON

when the accumulated power-ON time
exceeds the limit (B034)

OFF

when the accumulated power-ON time is
less than the limit (B034)

Valid for
outputs:

11, 12, AL0 – AL2

Required
settings:

B034

Notes:
The two outputs [RNT] and [ONT] share the

same time threshold parameter, B040.
Typically, you will use either the [RNT] or the
[ONT] output only—not both at once.

These outputs are useful for the notification

that a preventative maintenance interval has
expired.

RNT or

See I/O specs on page

4–8

.

ONT

Inverter output terminal circuit

12C

12A

11C

11A

+

24VDC

L

Example (requires output configuration—
see page

3–48

):