Chapter 3, Installation environment and noise measures, Heat radiation and installation – IAI America XSEL-KET User Manual

Page 24

Advertising
background image

5

INTELLIGENT ACTUATOR

Part 1 Installation

Chapter 3 Installation Environment and Noise Measures

1. Installation Environment

As for the use environment, this product can be used in an environment of pollution degree 2

*1

or

equivalent.

*1 Pollution degree 2: Normally only non-conductive pollutants exist, which are expected to be

temporarily conductive due to condensation. (IEC60664-1)

(1) When installing and wiring the controller, do not block the ventilation holes provided for cooling.

(Insufficient ventilation will not only prevent the product from functioning fully, but it may also result in

failure.)

(2) Prevent foreign matter from entering the controller through the ventilation holes. Since the controller is

not designed as dustproof or waterproof (oilproof), avoid using it in a dusty place or place subject to

oil mist or splashed cutting fluid.

(3) Do not expose the controller to direct sunlight or radiant heat from a high heat source such as a heat-

treating furnace.

(4) Use the controller in a non-condensing environment free from corrosive or inflammable gases.

(5) Use the controller in an environment where it will not receive external vibration or impact.

(6) Prevent electrical noise from entering the controller or its cables.

Environmental Condition of Controller

n

o

it

a

c

if

i

c

e

p

S

m

e

tI

Surrounding air temperature range

0?C ~ 40?C

Forced air-cooling

24 VDC fan x 5 (2-axis type)

24 VDC fan x 6 (4-axis type)

Surrounding humidity range

30% ~ 85%

Storage temperature range

-10?C ~ 65?C

Dust protection structure

IP20

Power-source voltage

230 VAC, single-phase

Operating power-source voltage

?

10%

Rated operating power-source

frequency

50 Hz/60 Hz

2. Heat Radiation and Installation

Design the control panel size, controller layout and cooling method so that the surrounding air

temperature around the controller will be kept at or below 40°C.

Install the controller vertically on a wall, as illustrated below. The controller will be cooled by forced

ventilation (exhaust air will be discharged from the top). Be sure to install the controller in the

aforementioned direction and provide a minimum clearance of 150 mm above and 150 mm below the

controller.

If multiple controllers are to be installed side by side, providing additional suction fans on top of the

controllers will help maintain a uniform surrounding air temperature.

Provide a minimum clearance of 150 mm between the front side of the controller and a wall

(enclosure).