2.1

System I/O Connector


The table below summarizes the detailed explanations of the respective terminals of the system I/O
connector.

1

RDY OUT1

2

RDY OUT2

A dry contact indicating that the controller has started properly.
The contact capacity is 24 VDC, 1 A max.
Use this contact for safety circuit interlocking.

3

S.GATE IN

4

+24V OUT

A safety-gate operation monitor input signal that always remains
enabled regardless of the operating mode of the controller. The
contact-A input operates the actuator only in MAKE mode. Connect it to
the dry contact for safety-gate signal from the external safety circuit.
This input must be shorted if not used.

5

EMG IN

6

+24V OUT

An emergency-stop operation monitor input signal. The contact-B input
actuates an emergency stop in BREAK mode. Short this input if a relay
box is used.

Note) 24V OUT in Nos. 4 and 6 is a dedicated output generated inside the controller. Never use

it for any other purpose.