1 system i/o connector – IAI America XSEL-KET User Manual
Page 52

33
INTELLIGENT ACTUATOR
Part 1 Installation
2.1
System I/O Connector
The table below summarizes the detailed explanations of the respective terminals of the system I/O
connector.
1
RDY OUT1
2
RDY OUT2
A dry contact indicating that the controller has started properly.
The contact capacity is 24 VDC, 1 A max.
Use this contact for safety circuit interlocking.
3
S.GATE IN
4
+24V OUT
A safety-gate operation monitor input signal that always remains
enabled regardless of the operating mode of the controller. The
contact-A input operates the actuator only in MAKE mode. Connect it to
the dry contact for safety-gate signal from the external safety circuit.
This input must be shorted if not used.
5
EMG IN
6
+24V OUT
An emergency-stop operation monitor input signal. The contact-B input
actuates an emergency stop in BREAK mode. Short this input if a relay
box is used.
Note) 24V OUT in Nos. 4 and 6 is a dedicated output generated inside the controller. Never use
it for any other purpose.