68

INTELLIGENT ACTUATOR

Part 3 Controller Data Structure


[3] Power ON with drive-source cutoff input still effective




















































* If the contact status of the system I/O “RDY OUT” is not provided to the external input for drive-source

cutoff, Error No. D6E, “Motor drive-source OFF error (MPONSTR-OFF)” may also occur when a cold-
start level alarm occurs. However, this does not present any problem.

Power ON

Control power (AC)

External input for
drive-source cutoff
(Emergency stop
switch, etc.)

Reset

System I/O
RDY OUT

Drive-source
cutoff/reset

Servo ON command

Be sure to reset within 200 ms.

Provide at least 1 sec.

[4] Occurrence of cold-start level alarm during operation

Control power (AC)

External input for
drive-source cutoff
(Emergency stop
switch, etc.)

Occurrence of alarm
Cold-start level

System I/O
RDY OUT

Drive-source cutoff/reset

Occurrence of alarm

The RDY OUT contacts break upon
occurrence of a cold-start level error.

Within 200 ms

Although the RDY OUT contacts close, the internal
status of the X-SEL controller will not change to
“Drive-source cutoff reset” until the external input
for drive-source cutoff is reset.