Troubleshooting (Causes and Countermeasures for Key Errors)

Error No.

Error name

Cause

Countermeasure

ACF

AC power cutoff

Momentary power failure has occurred or
the voltage has dropped.
100 V is input while the controller’s voltage
specification is 200 V.

Check the power-source voltage.
If the last digit of the controller’s model number is “-1,”
the power specification is 100 V. If the last digit is “-2,”
the power specification is 200 V.

ErG Emergency

stop

(This is not an error.)

Emergency-stop signal is input.

Emergency-stop signal is input in the following
condition:
1. The emergency-stop button on the teaching

pendant is pressed.

2. The applicable input terminal in the system

connector is turned ON.

3. The port switch on the front panel is set to the

manual side.
(The teaching-pendant/PC-software connector is
not connected.)

4. The actuator is of sensor specification and the slider

is stopped on either end of the slider.

oPG

Safety gate open

The safety gate is open.

Check the system connector wiring.

dSF

Deadman switch OFF

The switch is set to the manual side even
when the teaching-pendant connector or
other connector is not connected.

Set the switch to the auto side when the teaching-
pendant connector or other connector is not connected.

C9C

Defective phase-Z position
error

The phase-Z position is defective or the
reversing amount at home return is small.

Check to see if foreign object has entered the actuator.
Check to see if the mounting bolts are contacting the
slider.
* Change axis-specific parameter No. 22 to “100.”