70

INTELLIGENT ACTUATOR

Part 3 Controller Data Structure

[6] Emergency stop switch/safety gate/deadman switch input and drive-source cutoff/reset

(When combined with the drive-source recovery request signal [I/O parameter No. 44 = 1])

* In the MANU mode, do not reset the drive-source cutoff while the PC connection cable is connected

and the PC software is not running.

In the above condition, the drive-source recovery request cannot be accepted (PIO start is prohibited),

and thus Error No. E6D, “Drive-source cutoff relay error” will occur if the drive-source cutoff is reset.

Control power (AC)

External input for

drive-source cutoff

(Emergency stop

switch, etc.)

Drive-source recovery

request signal

(I/O port IN14)

System I/O

RDY OUT

Drive-source

cutoff/reset

Servo ON command

If I/O Parameter No. 24 = 0, RDY Out turns OFF when the emergency stop turns ON. In such a case,

wait till RDY OUT turns ON before inputting the drive recovery demand signal.

Provide at least 1 sec.

The RDY OUT contacts

do not open even when

the drive source is cut off.

least 5 sec.

Cut off

Reset

Within 200 ms

If the drive source is cut off and the cutoff is

reset repeatedly, provide an interval of at

Be sure to reset within 200 ms.