IAI America XSEL-KET User Manual
Page 26
7
INTELLIGENT ACTUATOR
Part 1 Installation
*
Notes on wiring method
Use twisted cables for the AC power cable and 24-VDC external power cable. Wire the controller
cables separately from lines creating a strong electric field such as power circuit lines (by not bundling
them together or placing in the same cable duct).
If you wish to extend the motor cable or encoder cable beyond the length of each supplied cable,
please contact IAI.
(2) Noise-elimination grounding
Provide a dedicated grounding of the FG or PE grounding point.
(3) Noise sources and noise elimination
There are many noise sources, but solenoid valves, magnet switches and relays are of particular
concern when building a system. Noise from these parts can be eliminated using the measures
specified below:
a. AC solenoid valve, magnet switch, relay
Measure --- Install a surge killer in parallel with the coil.
AC power source
Class D grounding
Metal enclosure
Connect the FG terminal
with the metal enclosure
using a cable of a maximum
allowable size over the
shortest distance.
Surge killer
Point
Wire from each coil over the shortest distance.
Installing a surge killer on the terminal block,
etc., will be less effective because of a longer
distance from the coil.
C.POWER
N
L
PE
X-SEL
controller
Do not use this method.
Other
equipment
X-SEL
controller
Other
equipment