IAI America XSEL-KET User Manual

Page 392

Advertising
background image

Appendi

x

INTELLI

GENT A

CTUAT

OR

373

Description

Action Parameter

setting

Manipulation/operation

Want to output signal when the
actuator enters a specified area
(zone).

A desired actuator zone can be set for
each axis. A desired output port to turn
ON when the axis enters the zone can
be set for each axis. A maximum of four
zones can be set (zones 1 to 4).
Max. value of zone 1:

Axis-specific parameter No. 86

Min. value of zone 1:

Axis-specific parameter No. 87

Zone 1 output port number:

Axis-specific parameter No. 88


Max. value of zone 2:

Axis-specific parameter No. 89

Min. value of zone 2:

Axis-specific parameter No. 90

Zone 2 output port number:

Axis-specific parameter No. 91


Max. value of zone 3:

Axis-specific parameter No. 92

Min. value of zone 3:

Axis-specific parameter No. 93

Zone 3 output port number:

Axis-specific parameter No. 94


Max. value of zone 4:

Axis-specific parameter No. 95

Min. value of zone 4:

Axis-specific parameter No. 96

Zone 4 output port number:

Axis-specific parameter No. 97

Setting example) Set the area illustrated
below as zone 1:
Axis 1: Output port No. 311 will turn ON

when the axis enters the area
between 150 and 200 mm.

Axis 2: Output port No. 312 will turn ON

when the axis enters the area
between 75 and 125 mm.












Axis 1

Axis 2

Axis-specific
parameter
No. 86

200000 125000

*

Axis-specific
parameter
No. 87

150000 75000

*

Axis-specific
parameter
No. 88

311 312

*: Max. and min. values are input in

units of 0.001 mm.

For the output signal to be processed,
the axes must stay for at least 3 msec in
the zone. Duplicate output port numbers
cannot be specified.








: Output port No. 311 turns
ON.

: Output port No. 312 turns
ON.

Before changing a parameter, be sure to read the corresponding section in the List of Parameters.

Axis 2

Axis 1

125

75

0 150

200