5. Modbus RTU

96

Modbus

(4) Query sample

A sample query that reads the system status (from address 9008

H

) of a controller of axis No. 0 is

shown below.

z

Query (silent intervals are inserted before and after the query)

01 03 90 08 00 02 68 C9

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Start address [H]

9008

Number of registers [H] 0002

Error check [H]

68C9 (in accordance with

CRC calculation)

End

Silent interval

The response to the query is as follows.

z

Response (silent intervals are inserted before and after the response)

01 03 04 00 0C 00 17 7A 3E

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Number of data bytes [H] 04 (4 bytes = 2 registers)

Data 1 [H]

00 0C 00 17

Error check [H]

7A3E (in accordance with CRC calculation)

End

Silent interval

Note The data of the response example is simply an example and will vary depending on

various conditions.