5. Modbus RTU
96
Modbus
(4) Query sample
A sample query that reads the system status (from address 9008
H
) of a controller of axis No. 0 is
shown below.
z
Query (silent intervals are inserted before and after the query)
01 03 90 08 00 02 68 C9
Field
RTU mode
8-bit data
Start
Silent interval
Slave address [H]
01
Function code [H]
03
Start address [H]
9008
Number of registers [H] 0002
Error check [H]
68C9 (in accordance with
CRC calculation)
End
Silent interval
The response to the query is as follows.
z
Response (silent intervals are inserted before and after the response)
01 03 04 00 0C 00 17 7A 3E
Field
RTU mode
8-bit data
Start
Silent interval
Slave address [H]
01
Function code [H]
03
Number of data bytes [H] 04 (4 bytes = 2 registers)
Data 1 [H]
00 0C 00 17
Error check [H]
7A3E (in accordance with CRC calculation)
End
Silent interval
Note The data of the response example is simply an example and will vary depending on
various conditions.