Modbus – IAI America ROBO Cylinder Series User Manual

Page 122

Advertising
background image

5. Modbus RTU

114

Modbus

(4) Query sample

An example of use is shown, where the current measurement on the load cell connected to

controller axis 0 is read.

z

Query (silent intervals are inserted before and after the query)

01 03 90 0A 00 02 89 0D

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Start address [H]

901E

Number of registers [H] 0002

Error check [H]

890D (in accordance with

CRC calculation)

End

Silent interval

The response to the query is as follows.

z

Response (silent intervals are inserted before and after the response)

01 03 04 00 00 03 E4 FA 88

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Number of data bytes [H] 04 (4 bytes = 2 register)

Data 1 [H]

00 00 03 E4

Error check [H]

FA88 (in accordance with CRC

calculation)

End

Silent interval

Example 1) The current measurement on the load cell is “000003E4,”convert into a decimal

number, or 996 (x 0.01 N) o The current push force is 9.96 N.

Example 2) If the current measurement reading on the load cell is “FFFFFF35”

(tensile state

(Note 2)

), the formula FFFFFFFF

H

– FFFFFF35

H

+ 1 (1 must be added)

applies.

The result is converted into decimal number, or 203 (x 0.01 N) o

The current tensile force

(Note 2)

is 2.03 N.

Note 1

This is only one example of response. The specific response varies depending on

each situation.

Note 2

Load cell cannot be used for pulling operation.