(2) Cable Wiring

Ɣ Use our company’s genuine cables for connecting between the actuator and

controller, and for the teaching tool.

Ɣ Do not scratch on the cable. Do not bend it forcibly. Do not pull it. Do not coil it

around. Do not insert it. Do not put any heavy thing on it. Failure to do so may

cause a fire, electric shock or malfunction due to leakage or continuity error.

Ɣ Perform the wiring for the product, after turning OFF the power to the unit, so that

there is no wiring error.

Ɣ When the direct current power (+24V) is connected, take the great care of the

directions of positive and negative poles. If the connection direction is not correct, it

might cause a fire, product breakdown or malfunction.

Ɣ Connect the cable connector securely so that there is no disconnection or

looseness. Failure to do so may cause a fire, electric shock or malfunction of the

product.

Ɣ Never cut and/or reconnect the cables supplied with the product for the purpose of

extending or shortening the cable length. Failure to do so may cause the product to

malfunction or cause fire.

4 Installation

and Start

(3) Grounding

Ɣ The grounding operation should be performed to prevent an electric shock or

electrostatic charge, enhance the noise-resistance ability and control the

unnecessary electromagnetic radiation.

Ɣ For the ground terminal on the AC power cable of the controller and the grounding

plate in the control panel, make sure to use a twisted pair cable with wire thickness

0.5mm

2

(AWG20 or equivalent) or more for grounding work. For security

grounding, it is necessary to select an appropriate wire thickness suitable for the

load. Perform wiring that satisfies the specifications (electrical equipment technical

standards).

Ɣ Perform Class D Grounding (former Class 3 Grounding with ground resistance

100: or below).