5. Modbus RTU

142

Modbus

5.4.15 Load Cell Calibration Command <<CLBR>> --- A dedicated load cell must be

connected.

(1) Function --- SCON-CA only

The dedicated load cell is calibrated.

The factory setting of your load cell is that the ON status corresponds to a no-load state. If you

want to define the reference state as a condition where a work part (load) is installed, calibrate

the load cell.

Also calibrate the load cell in other situations as necessary (readjustment, inspection, etc.).

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is

specified

Function code [H]

1

05

Write to a single coil DO

Start address [H]

2

0426

Load cell calibration

command

Changed data [H]

2

Arbitrary

Calibration command: FF00

H

Normal operation: 0000

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Calibration procedure

[1] Stop the actuator operation. (The load cell cannot be calibrated while the actuator is

performing any axis operation or push-motion operation or being paused, in which case 0E1

(load cell calibration error) alarm generates.)

[2] Turn this signal ON and keep it ON for at least 20 ms.

[3] When the calibration is complete, the calibration complete signal (CEND of device status

register 1 explained in 4.3.2 (12)) turns ON. After confirming that the CEND has turned ON,

turn OFF the CLBR.

If the calibration was unsuccessful, a 0E1 (load cell calibration error) alarm generates.

Caution: Normal operation commands are not accepted while the CLBR is ON.