Modbus – IAI America ROBO Cylinder Series User Manual

Page 112

Advertising
background image

5. Modbus RTU

104

Modbus

(4) Query sample

A sample query that reads the system timer value (from address 9010

H

) of a controller of axis No.

0 is shown below.

Query (silent intervals are inserted before and after the query)

01 03 90 10 00 02 E8 CE

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Start address [H]

9010

Number of registers [H] 0002

Error check [H]

E8CE (in accordance with

CRC calculation)

End

Silent interval

The response to the query is as follows.

Response (silent intervals are inserted before and after the response)

01 03 04 00 02 7A 72 F8 B6

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Number of data bytes [H] 04 (4 bytes = 2 registers)

Data 1 [H]

00 02 7A 72

Error check [H]

F8B6 (in accordance with CRC calculation)

End

Silent interval

The system timer is “00027A72” o Convert into decimal number o 162418 (ms)

The total time since the controller power was turned on is 162.418 sec.

Note The data of the response example is simply an example and will vary depending on

various conditions.