Modbus – IAI America ROBO Cylinder Series User Manual
Page 140
5. Modbus RTU
132
Modbus
5.4.10 Teaching Mode Command <<MOD>>
(1) Function
This bit switches between the normal operation mode and teaching mode.
(2) Query format
Field
Number of data items
(number of bytes)
RTU mode
8-bit data
Remarks
Start
None
Silent interval
Slave address [H]
1
Arbitrary
Axis number + 1 (01
H
to 10
H
)
00
H
when broadcast is
specified
Function code [H]
1
05
Write to a single coil DO.
Start address [H]
2
0414
Switch between the normal
mode and the teaching mode.
Changed data [H]
2
Arbitrary
Teaching mode: FF00
H
Normal operation mode: 0000
H
Error check [H]
2
CRC (16 bits)
End
None
Silent interval
Total number of bytes
8
(3) Response
If the change is successful, the response message will be the same as the query.
If invalid data is sent, an exception response (refer to section 7) will be returned, or no response
will be returned.