Modbus – IAI America ROBO Cylinder Series User Manual

Page 56

Advertising
background image

4. Communicationn

48

Modbus

(17) Data of zone status register (Address = 9013

H

) (ZONS)

Bit

Symbol

Name

Function

15

-

Cannot be used

14

LS2

Limit sensor output monitor 2

(PCON-C/CG/CA/CFA,

ACON-C/CG,

SCON

PIO pattern 5)

0: Out of range

1: In range

The negative boundary of the positioning band is obtained by subtracting

the positioning band size from target position No. 2 while the positive

boundary of the positioning band is obtained by adding the positioning

band size to target position No. 2.

This bit will become 1 when the current position is within the band and 0

when it is outside the band.

This bit becomes effective upon home return completion. It remains

effective even while the servo is OFF.

13

LS1

Limit sensor output monitor 1

(PCON-C/CG/CA/CFA,

ACON-C/CG,

SCON

PIO pattern 5)

0: Out of range

1: In range

The negative boundary of the positioning band is obtained by subtracting

the positioning band size from target position No. 1 while the positive

boundary of the positioning band is obtained by adding the positioning

band size to target position No. 1. This bit remains 1 as long as the

current position is within these boundaries.

This bit will become 1 when the current position is within the band and 0

when it is outside the band.

This bit becomes effective upon home return completion. It remains

effective even while the servo is OFF.

12

LS0

Limit sensor output monitor 0

(PCON-C/CG/CA/CFA,

ACON-C/CG,

SCON

PIO pattern 5)

0: Out of range

1: In range

The negative boundary of the positioning band is obtained by subtracting

the positioning band size from target position No. 0 while the positive

boundary of the positioning band is obtained by adding the positioning

band size to target position No. 0. This bit remains 1 as long as the

current position is within these boundaries.

This bit will become 1 when the current position is within the band and 0

when it is outside the band.

This bit becomes effective upon home return completion. It remains

effective even while the servo is OFF.

11

-

Cannot be used

10

-

Cannot be used

9

-

Cannot be used

8

ZP

Position zone output

monitor

0: Out of range

1: In range

This bit remains 1 while the current position is within the zone range

specified for each position and becomes 0 when it is outside the range.

This bit becomes effective upon home return completion. It remains

effective even while the servo is OFF.

7

-

Cannot be used

6

-

Cannot be used

5

-

Cannot be used

4

-

Cannot be used

3

-

Cannot be used

2

-

Cannot be used

1

Z2

Zone output monitor 2

0: Out of range

1: In range

This bit remains 1 while the current position is within the range where the

zone boundary 2 parameter is set and becomes 0 when it is outside the

range.

This bit becomes effective upon home return completion. It remains

effective even while the servo is OFF.

0

Z1

Zone output monitor 1

0: Out of range

1: In range

This bit remains 1 while the current position is within the range where the

zone boundary 1 parameter is set and becomes 0 when it is outside the

range.

This bit becomes effective upon home return completion. It remains

effective even while the servo is OFF.

Advertising