6. Modbus

ASCII

268

Modbus

6.5.16 PIO/Modbus Switching Setting <<PMSL>>

(1) Function

PIO external command signals can be enabled or disabled.

(2) Query format

Field

Number of

characters

ASCII mode

character string

(fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1 (01

H

to 10

H

)

00

H

when broadcast is specified

Function code [H]

2

‘0’, ‘5’

Write to a single coil DO.

Start address [H]

4

‘0’, ‘4’, ‘2’, ‘7’

PIO/Modbus switching setting

Changed data [H]

4

Arbitrary

*1 Enable Modbus commands: ‘F’, ‘F’, ‘0’, ‘0’

Disable Modbus commands: ‘0’, ‘0’, ‘0’, ‘0’

Error check [H]

2

LRC calculation

result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

*1 x Enable Modbus commands (ON) (disable PIO command): FF00

H

Operation via PIO signals is not possible.

x

Disable Modbus commands (OFF) (enable PIO command): 0000

H

Operation via external PIO signals is possible.

Supplement If the Modbus command is enabled, the PIO status at change is maintained.

If the Modbus command is switched to disabled, the operation status changes

according to the current PIO status. Note that even if the status of signals that

operate via edge detection has been changed, edge detection is ignored.

(3) Precaution

„

On a model equipped with an operation mode switch, “Enable PIO commands” will be specified

when the switch is set to the AUTO mode, or “Disable PIO commands” will be specified when the

switch is set to the MANU mode.

„

On a non-PIO model, the default setting is “Disable PIO commands.”

„

If IAI’s tool (teaching pendant or PC software) is connected, “Teaching modes 1, 2” and “Monitor

modes 1, 2” are available as tool modes. The correspondence between these modes and PIO

enable/disable specifications are as follows:

“Monitor modes 1, 2” o “Enable PIO commands”

“Teaching modes 1, 2” o “Disable PIO commands”