5. Modbus RTU

72

Modbus

5.3.5 Present Time Reading <<TIMN>>

(1) Function

This bit reads the present time.ᴾ

[Dedicated for PCON-CA/CFA and SCON-CA]

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

Refer to remarks

841A: SCON-CA

8420: PCON-CA/CFA

Number of registers [H]

2

0002

Reading addresses 8402

H

to

8403

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Number of data bytes [H]

1

04

Reading 2 registers = 4 bytes

Data [H]

4

Present Time

Refer to (4) for conversion at

time.

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

9