6. Modbus

ASCII

205

Modbus

6.4.9 I/O Port Input Signal Status Reading <<DIPM>>

(1) Function

Port input values of the RC controller are read directly regardless of the PIO pattern. Note that the

values are the states of ports recognized by the RC controller as inputs.

(2) Query format

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Reading registers

Start address [H]

4

‘9’, ‘0’, ‘0’, ‘3’

Input port monitor register

Number of registers [H]

4

‘0’, ‘0’, ‘0’, ‘1’

Reading address 9003

H

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

17

(3) Response format

A response message contains 16 bits of data per address.

Field

Number of characters ASCII mode character

string (fixed)

Remarks

Header

1

‘:’

Slave address [H]

2

Arbitrary

Axis number + 1

(01

H

to 10

H

)

Function code [H]

2

‘0’, ‘3’

Reading registers

Number of data bytes [H]

2

‘0’, ‘2’

Reading 1 register

= 2 bytes

Data 1 [H]

4

DI input value

DI input value [Hex]

Error check [H]

2

LRC calculation result

Trailer

2

‘CR’, ‘LF’

Total number of bytes

15