Modbus – IAI America ROBO Cylinder Series User Manual

Page 218

Advertising
background image

6. Modbus

ASCII

210

Modbus

(4) Sample query (Axis No. 0)

A sample query that reads input ports (address 9004

H

) in a controller of axis No. 0 is shown below.

Query: 01039004000167[CR][LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Start address [H]

‘9’, ‘0’, ‘0’, ‘4’

39303034

Number of registers [H] ‘0’, ‘0’, ‘0’, ‘1’

30303031

Error check [H]

‘6’, ‘7’ (in accordance with LRC calculation)’ 3637

End

‘CR’, ‘LF’

0D0A

The response to the query is as follows.

Response: 010302740086[CR][LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Number of data bytes [H] ‘0’, ‘2’ (2 bytes = 1 register)

3032

Data 1 [H]

‘7’, ‘4’, ‘0’, ‘0’

37343030

Error check [H]

‘8’, ‘6’ (in accordance with LRC calculation) 3836

End

‘CR’, ‘LF’

0D0A

The output port data area is “7400”

H

o

Convert into binary number “0111010000000000”

Note The data of the response example is simply an example and will vary depending on various

conditions