Modbus – IAI America ROBO Cylinder Series User Manual

Page 201

Advertising
background image

6. Modbus

ASCII

193

Modbus

(4) Query sample

A sample query that reads the Total moving count (addresses 8400

H

to 8401

H

) of a controller with

axis No. 0 is shown below.

Query: 01038400000276 [CR][LF]

Field

ASCII mode

fixed character string

Converted ASCII code

data [H]

Header

‘:’

3A

Slave address

‘0’, ‘1’

3031

Function code

‘0’, ‘3’

3033

Start address

‘8’, ‘4’, ‘0’, ‘0’

38343030

Number of registers

‘0’, ‘0’, ‘0’, ‘2’

30303032

Error check

‘7’, ‘6’ (in accordance with

CRC calculation)

3736

Trailer

‘CR’, ‘LF’

0D0A

The response to the query is as follows.

Response: 0103040000021FD7[CR][LF]

Field

ASCII mode

fixed character string

Converted ASCII code

data [H]

Header

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Number of data bytes [H] ‘0’, ‘4’

3034

Data 1 [H]

‘0’, ‘0’, ‘0’, ‘0’

30303030

Data 2 [H]

‘0’, ‘2’, ‘1’, ‘F’

30323146

Error check [H]

‘D’, ‘7’ (in accordance with

LRC calculation)

4337

Trailer

‘CR’, ‘LF’

0D0A

The Total moving count is “21F

H

” o Convert into decimal number o 543[times]

Note The data of the response example is simply an example and will vary depending on various

conditions.