5. Modbus RTU

81

Modbus

5.3.9 I/O Port Input Signal Status Reading <<DIPM>>

(1) Function

This query reads the port input value of the RC controller regardless of the PIO pattern.

The status of the port to which a signal is currently input as recognized by the RC controller is

read.

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

9003

Input port monitor register

Number of registers [H]

2

0001

Reading address 9003

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per address.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Number of data bytes [H]

1

02

Reading 1 register = 2 bytes

Data 1 [H]

2

Port input value

Port input value [Hex]

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

7