Modbus – IAI America ROBO Cylinder Series User Manual

Page 316

Advertising
background image

7. T

roubleshooting

308

Modbus

Continued from the previous page

Cannot communicate with specific controllers.

[1] Wrong wiring of communication cables between controllers and junction o Check wiring *3

[2] Device power supply error o Check power supply voltage o Check that the 0 V line is used

commonly for all devices o Use the 0 V line commonly for all devices.

Cannot communicate from time to time?

[1] Malfunction due to noise o

(1) Decrease the communication speed Check *2
(2) Change communication cable wiring Check *7
(3) Check connection of FG of each RC controller *7
(4) Mount a clamp filter on the power lines
(5) Check grounding of the control board *7

[2] Inadequate host programs o

Check programs again (occurrence of communication buffer overflow, etc.?)