5. Modbus RTU

68

Modbus



5.3.3 Total moving count Reading <<TLMC>>

(1) Function

This bit reads the total moving count.

[Refer to Section 4.3.2(8)]

(2) Query format

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Start address [H]

2

8400

Total moving count

Number of registers [H]

2

0002

Reading addresses 8400

H

to

8401

H

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

8

(3) Response format

A response message contains 16 bits of data per register.

Field

Number of data items

(number of bytes)

RTU mode

8-bit data

Remarks

Start

None

Silent interval

Slave address [H]

1

Arbitrary

Axis number + 1 (01

H

to 10

H

)

Function code [H]

1

03

Register reading

Number of data bytes [H]

1

04

Reading 2 registers = 4 bytes

Data 1 [H]

2

Total moving count

Total moving count(0500

H

)

[Hex] (most significant digit)

Data 2 [H]

2

Total moving count

Total moving count(0501

H

)

[Hex] (least significant digit)

Error check [H]

2

CRC (16 bits)

End

None

Silent interval

Total number of bytes

9