Modbus – IAI America ROBO Cylinder Series User Manual

Page 75

Advertising
background image

5. Modbus RTU

67

Modbus

(4) Query sample

A sample query that reads the contents of last occurred alarm (addresses 0500

H

to 0505

H

) of a

controller with axis No. 0 is shown below.

z

Query (silent intervals are inserted before and after the query)

01 03 05 00 00 06 C5 04

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Start address [H]

0500

Number of registers [H] 0006

Error check [H]

C504 (in accordance with

CRC calculation)

End

Silent interval

The response to the query is as follows.

z

Response (silent intervals are inserted before and after the response)

01 03 0C 00 00 FF FF 00 00 00 E8 17 2C 64 3F 2D CD

Field

RTU mode

8-bit data

Start

Silent interval

Slave address [H]

01

Function code [H]

03

Number of data bytes [H] 0C (12 bytes = 6 registers)

Data 1 [H]

00 00 (Alarm detail code)

Data 2 [H]

FF FF (Alarm address)

Data 3 [H]

00 00 00 E8 (Alarm code)

Data 4 [H]

17 2C 64 3F (Alarm occurrence time)

Error check [H]

2DCD (in accordance with CRC calculation)

End

Silent interval

Alarm detail code:

0000

H

xxxx

No detail code

Alarm address:

FFFF

H

xxx

Disable (no detail code)

Alarm code:

00E8

H

=0E8xxxEncoder AB phase break error

Alarm occurrence time: 172C643F

H

(conversion) Ÿ2012/04/26 19:53:35 [Conversion is

refer to the Section 4.3.2(3)]

Note 1 The data of the response example is simply an example and will vary depending on

various conditions.

Note 2 For the detail of an alarm code, check in the instruction manual of the each

controller.