6. Modbus

ASCII

206

Modbus

(4) Sample query (Axis No. 0)

A sample query that reads input ports (address 9003

H

) in a controller of axis No. 0 is shown below.

Query: 01 03 90 03 00 01 68 [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Start address [H]

‘9’, ‘0’, ‘0’, ‘3’

39303033

Number of registers [H] ‘0’, ‘0’, ‘0’, ‘1’

30303031

Error check [H]

‘6’, ‘8’ (In accordance with LRC calculation)’ 3638

End

‘CR’, ‘LF’

0D0A

The response to the query is as follows.

Response: 01 03 02 B8 01 14 [CR] [LF]

Field

ASCII mode

fixed character string

Converted ASCII

code data [H]

Start

‘:’

3A

Slave address [H]

‘0’, ‘1’

3031

Function code [H]

‘0’, ‘3’

3033

Number of data bytes [H] ‘0’, ‘2’ (2 bytes = 1 register)

3032

Data 1 [H]

‘B’, ‘8’, ‘0’, ‘1’

42383031

Error check [H]

‘1’, ‘4’ (in accordance with LRC calculation) 3134

End

‘CR’, ‘LF’

0D0A

The input port data area is “B801”

H

o

Convert into binary number “1011100000000001”

Note The data of the response example is simply an example and will vary depending on various

conditions.