Modbus – IAI America ROBO Cylinder Series User Manual

Page 319

Advertising
background image

7. T
roubleshooting

311

Modbus

*6 Refer to section 3.6 to check the communication speed setting again.

Set the same communication speed for all RC controllers as well as the host.

Check (2) in *5.

*7 Wire communication cables such that they do not run in parallel with power cables and cables

that send pulse signals.

Check that the communication cable is properly shielded (recommendation: 1-point ground).

Check that the setting environment and noise countermeasures live up to the specifications

given in the instruction manual of each RC controller.

If the problems are not solved after checking above step, please contact us.

In this case, please let us know about the phenomena occurring and the result of checking the

items in the flowchart as well.